AGM POWER SYSTEMS
|
|
KOHLER HOME STANDBY GENERATORS
|
Kohler Co. provides one-source responsibility for the generating system and accessories.
- The generator set and its components are prototype-tested, factory-built ,and production-tested.
The 60 Hz generator set is UL 2200 listed.
- The generator set accepts rated load in one step.
- Safer Power for Sensitive Electronics
- A one-year limited warranty covers all systems and components. Two- and five-year extended warranties are also available.
Alternator features:
- The Fast-Response III wound field (WF) design alternator provides excellent voltage response and short-circuit capability using an auxiliary power brushless exciter.
- The unique Fast-Response II excitation system delivers excellent voltage response and short circuit capability using a permanent magnet (PM)-excited alternator.
- The brushless, rotating-field alterantor has broadrange reconnectability.
- NEMA MG1 ,IEEE, and ANSI standards compliance for temperature rise and motor starting.
- Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.
- Sustained short-circuit current enabling down stream circuit breakers to trip without collapsing the alternator field.
- Self-ventilated and dripproof construction.
- Vacuum-impregnated windings with fungus-resistant epoxy varnish for dependability and long life.
- Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
- Fast-Response III wound field (WF) brushless alternator with auxiliary power brushless exciter for excellent load response.
- Fast-Response II brushless alternator with brushless exciter for excellent load response.
Other features:
- A rugged industrial gas engine delivers rated power at 1800 rpm (60 Hz) and 1500 rpm (50 Hz).
Controllers are available for all applications. See controller features inside.
- The electronic, isochronous governor incorporates an integrated drive-by-wire throttle body actuator delivering precise frequency regulation.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Prime Fuel Consumption Natural Gas/LP, m3/hr. (cfh) at 50% load: |
9.7 m³/hr (344 cfh) |
|
Engine Manufacturer:
|
General Motors
|
|
Hertz:
|
60 Hz
|
|
Standby Ratings, kW(kVa):
|
42 kW (53 kVa)
|
|
Standby Fuel Consumption Natural Gas/LP, m3/hr. (cfh) at 25% load:
|
7.7 m³/hr (272 cfh)
|
|
Rating in KW:
|
45 kW
|
|
Standby Fuel Consumption Natural Gas/LP, m3/hr. (cfh) at 75% load:
|
13.8 m³/hr (486 cfh)
|
|
Standby Fuel Consumption Natural Gas/LP, m3/hr. (cfh) at 100% load:
|
16.5 m³/hr (584 cfh)
|
| Engine Model: |
Industrial Powertrain Vortec 4.3L |
| Alternator Type: |
Brushless, Permanent-Magnet
Wound Exciter Field with Separate Excitation Power Winding |
| Prime Fuel Consumption Natural Gas/LP, m3/hr. (cfh) at 100% load: |
15.5 m³/hr (548 cfh) |
| Prime Ratings, kW(kVa): |
38 kW (48 kVa) |
|
Max Power at rated rpm kWm (BHP):
|
56 kWm (75 BHP)
|
|
Standby Fuel Consumption Natural Gas/LP, m3/hr. (cfh) at 50% load:
|
10.2 m³/hr (360 cfh)
|
|
Cylinder Arrangement:
|
V-6
|
|
Fuel Type:
|
Natural Gas
|
| Prime Fuel Consumption Natural Gas/LP, m3/hr. (cfh) at 25% load: |
7.5 m³/hr (264 cfh) |
|
Prime Fuel Consumption Natural Gas/LP, m3/hr. (cfh) at 75% load:
|
12.8 m³/hr (452 cfh)
|
|
|
|
|
|
|
|
 |