AGM POWER SYSTEMS
|
|
GENERAC GUARDIAN QUIETSOURCE
16 kW Air-Cooled Standby Generator
|

Big Generator Protection… Half the Price
More power, more features and an exceptional price make the GUARDIAN QuietSource 16 kW the best value in automatic standby generators. With GUARDIAN’s new breakthrough technology, the 16 kW provides the circuit protection of a much larger generator at a truly remarkable price. If you need to run more than one air conditioner, the GUARDIAN QuietSource 16 kW is the affordable solution. With 33% more circuit coverage than our 13 kW, this powerhouse can start a 5-ton AND a 3-ton, or two 4-ton air conditioners with plenty of power to spare.
Whisper Quiet Operation
GUARDIAN’s exclusive patent-pending Whisper-Test low speed exercise feature makes the GUARDIAN QuietSource 16 kW the quietest air-cooled generator on the market. Whisper-Test reduces noise to less than 59 dBA during the weekly automatic self-test. That’s quieter than your central air conditioner.
With our pre-packaged, 16-circuit pre-wired system, installation is fast, easy and inexpensive, making the 16 kW an even better value.
- Breakthrough Design: Newly designed alternator can start a 5-ton AND a 3-ton*, or two 4-ton* air conditioners with plenty of power to spare
- Circuit Coverage: Protects 16 circuits of your home
- Automatic Voltage Regulator: Quality electrical output for sensitive electronics
- Electronic Governor: Fast response to changing electrical loads
- Whisper-Test: Patent-pending, self-test feature makes the GUARDIAN QuietSource quieter than your central air conditioner
- Generac OHVI® Industrial Engine: The ONLY air-cooled engine designed specifically for generators
- Longest Life Expectancy in the Industry: Over 3,000 hours of run time
- Full Pressure Lubrication: Continuous lubrication of all vital engine parts for protection from moment of start up for ultimate engine protection
- Spin-on Oil Filter: Automotive style for easy maintenance and prolonged engine life
- Superior Paint: Tough, textured powder coat paint finish for unmatched durability and all weather protection
- UL Listed: For safety and certified power ratings
- Clean Burning Fuel: Natural gas or LPV
| Rated Power LP (kW) |
16 |
| Rated Power NG (kW) |
15 |
| Voltage @ 60 Hz |
120/240 |
| Phase |
Single |
| Frequency |
60 Hz |
| Amps LP |
133.3/66.6 |
| Amps NG |
125.0/62.5 |
| Engine/Alternator RPM |
3600/3600 |
| Engine |
992cc
30 HP
Generac OHVI
V-Twin |
| Fuel Consumption LP (cu.ft./hr.)/(gal./hr.) |
92 (2.51) |
| Fuel Consumption NG (cu.ft./hr.) |
245 |
| EPA/CARB Certified |
Yes |
| Fuel |
Natural Gas/LP Vapor |
| Engine Cooling |
Air |
| Enclosure |
Steel |
| UL 2200 (US and Canada) |
Yes |
| Sound Output dB(A) at 23 ft. with generator operating at full load |
71.5 |
| Sound Output dB(A) at 23 ft. with generator in WhisperTest low speed exercise mode |
59 |
| Main Line Circuit Breaker |
65 Amp |
| Dimensions (L" x W" x H") |
48 x 24 x 28-1/4 |
| Unit Wt. (lbs.) |
445 |
|
Click for